E-Mail: overseas@onosokki.co.jp

Select your region & language

Global

Region

Digital Gauges: Frequently Asked Questions

Question number FAQ-0101

What is the successor to the DG-410?

There are two models with a comparator function: the DG4280 and the DG4240. The DG4280 has the same functionality as the comparator output of the DG410.

(1) DG4280

Output conditions (judgment criteria)Judgment output

Set polarity = Measured polarity
and
|Setting Value| ≤ |Measured Value|

The preset indicator light is red.

Preset output relay ON

BCD out connector: Preset output ON

(2) DG4240

The contact output specifications are categorized into three types: LOWER, OK, and UPPER.

Judgment criteriaJudgementDisplay and output of judgment results
LOWER setting value ≥ Displayed valueLOWER- The LOWER indicator light on the COMPARATOR indicator lights up red.
・LOWER output relays (NO.10, 11) ON
- SCD OUT connector LOWER output (pin 22) ON
LOWER setting value < Displayed value < UPPER setting valueOK- The COMPARATOR indicator light is green when it shows OK.
- OK output relay (No. 12 13) ON
- SCD OUT connector OK output (pin 22) ON
UPPER setting value ≤ Display valueUPPER- The UPPER indicator light on the COMPARATOR indicator lights up red.
・UPPER output relay (No. 14 15) ON
- BCD OUT connector UPPER output (pin 23) ON

For more details, please refer to the FAQs for DG4280 and DG4240.

Last updated: 2001-01-12